CTC EcoLogic

Room temp.

Heating circuit 1

0.0°C

(23.5)°C
Heating circuit 2

0.0°C

(23.5)°C

Night reduction heat circ. 1

Weekly programOff
Monday15-00 03-00
Tuesday15-00 03-00
Wednesday15-00 03-00
Thursday15-00 03-00
Friday15-00 03-00
Saturday15-00 03-00
Sunday15-00 03-00
DecreaseSunday 8:00
IncreaseSaturday 24:00
DecreaseSunday 6:30
IncreaseThursday 11:30


Night reduction heat circ. 2

Weekly programOff
Monday15-00 03-00
Tuesday15-00 03-00
Wednesday15-00 03-00
Thursday15-00 03-00
Friday15-00 03-00
Saturday15-00 03-00
Sunday15-00 03-00
DecreaseSunday 8:00
IncreaseSaturday 24:00
DecreaseSunday 6:30
IncreaseThursday 11:30


Night reduction heat circ. 3

Weekly programOff
Monday15-00 03-00
Tuesday15-00 03-00
Wednesday15-00 03-00
Thursday15-00 03-00
Friday15-00 03-00
Saturday15-00 03-00
Sunday15-00 03-00
DecreaseSunday 8:00
IncreaseSaturday 24:00
DecreaseSunday 6:30
IncreaseThursday 11:30


Night reduction heat circ. 4

Weekly programOff
Monday15-00 03-00
Tuesday15-00 03-00
Wednesday15-00 03-00
Thursday15-00 03-00
Friday15-00 03-00
Saturday15-00 03-00
Sunday15-00 03-00
DecreaseSunday 8:00
IncreaseSaturday 24:00
DecreaseSunday 6:30
IncreaseThursday 11:30


Holiday

Holiday period
10 days

Room temp.

Heating circuit 3

0.0°C

(23.5)°C
Heating circuit 4

0.0°C

(23.5)°C

DHW

Extra
hot water

On

7.5 hours
Temperature

Economic

Weekly program DHW

Weekly programOff
Monday15-00 03-00
Tuesday15-00 03-00
Wednesday15-00 03-00
Thursday15-00 03-00
Friday15-00 03-00
Saturday15-00 03-00
Sunday15-00 03-00


Operation data system

Operation data EcoLogic

Status:Add heat for heating
Primary flow 1 °C0 (55)
Return flow °C0
Heating circ pumpOn
Boilers/out °C0   0
Demand nbr of HP10
Degree minute-1000
Add heat1
Pool °C0   (22)

Stored oper data



Heating circuit 2-4

Solar panels

Status:Solar panel update Vaccuum
Outlet °C0
Inlet °C0
Pump Panel %30%
Pump Solar Charge %0%
Valve Solar charge TankDHW
Pump charge brine loopOff
Valve charge brine loopOff

Stored oper data

Settings for heat pump idA1
Total operation time h:134
Max primary flow °C0


Heating circuit 2-4

Mixing valve 2:Close
Room Temp 3 °C0.0   (20.0)
Primary flow 3 °C0   (20)
Radiator pump 3Off
Mixing valve 3Close
Room Temp 4 °C0.0   (20.0)
Primary flow 4 °C0   (55)
Radiator pump 4On
Mixing valve 4Open

Status heat pump

Compressor 1

Compressor:Blocked
Charge pumpOff   0%
Brine pumpOff
Brine in/ out °C:0.0   / 0.0
HP in/out °C0.0   / 0.0
Current L10.0

Compressor 2

Compressor:Blocked
Charge pumpOff   0%
Brine pumpOff
Brine in/ out °C:0.0   / 0.0
HP in/out °C0.0   / 0.0
Current L10.0

Compressor 3

Compressor:Blocked
Charge pumpOff   0%
Brine pumpOff
Brine in/ out °C:0.0   / 0.0
HP in/out °C0.0   / 0.0
Current L10.0

Compressor 4

Compressor:Blocked
Charge pumpOff   0%
Brine pumpOff
Brine in/ out °C:0.0   / 0.0
HP in/out °C0.0   / 0.0
Current L10.0

Compressor 5

Compressor:Blocked
Charge pumpOff   0%
Brine pumpOff
Brine in/ out °C:0.0   / 0.0
HP in/out °C0.0   / 0.0
Current L10.0

Compressor 6

Compressor:Blocked
Charge pumpOff   0%
Brine pumpOff
Brine in/ out °C:0.0   / 0.0
HP in/out °C0.0   / 0.0
Current L10.0

Compressor 7

Compressor:Blocked
Charge pumpOff   0%
Brine pumpOff
Brine in/ out °C:0.0   / 0.0
HP in/out °C0.0   / 0.0
Current L10.0

Compressor 8

Compressor:Blocked
Charge pumpOff   0%
Brine pumpOff
Brine in/ out °C:0.0   / 0.0
HP in/out °C0.0   / 0.0
Current L10.0

Compressor 9

Compressor:Blocked
Charge pumpOff   0%
Brine pumpOff
Brine in/ out °C:0.0   / 0.0
HP in/out °C0.0   / 0.0
Current L10.0

Compressor 10

Compressor:Blocked
Charge pumpOff   0%
Brine pumpOff
Brine in/ out °C:0.0   / 0.0
HP in/out °C0.0   / 0.0
Current L10.0

Operation data heating

Installer

Installer

Installer

Time09:30 
Date:2012-05-25


Installer

Installation:

Verify that the syst is

filled with water


Installation: Def System type

3

Installation: Def DHW tank

Yes

Installation: Compressor A1

Permitted

Installation:

Max primary flow °C,
heating circuit 1:
55

Installation:

Inclination,
heating circuit 1:
45

Installation:

Adjustment,
heating circuit 1:
0

Installation:

Max primary flow °C,
heating circuit 2:
55

Installation:

Inclination,
heating circuit 2:
45

Installation:

Adjustment,
heating circuit 2:
0

Settings

Heating circuit 1

Max primary flow °C55
Min primary flow °COff
Heating off, out °C18
Heating off, time120
Inclination °C50
Adjustment °C0
Room temp reduced-3
Heating circ pump speedAuto


Heating circuit 2

Max primary flow °C55
Min primary flow °COff
Heating off, out °C18
Heating off, time120
Inclination °C50
Adjustment °C0
Room temp reduced-3


Heating circuit 3

Max primary flow °C55
Min primary flow °COff
Heating off, out °C18
Heating off, time120
Inclination °C50
Adjustment °C0
Room temp reduced-3


Heating circuit 4

Max primary flow °C55
Min primary flow °COff
Heating off, out °C18
Heating off, time120
Inclination °C50
Adjustment °C0
Room temp reduced-3


Heat pump 1

Compressor A1Permitted
Start at degree minute-30
Max primary HP diff°C3
Max primary HP Add diff °C14
Diff between comp.-60
Prio A/W °C7
Cont. brine pump onNo
>>


Heat pump 2

Compressor A2Blocked
Cont. brine pump onNo
Compressor stop at brine°C-5
Brine pump on 10 daysOff


Heat pump 3

Compressor A3Blocked
Cont. brine pump onNo
Compressor stop at brine°C-5
Brine pump on 10 daysOff


Heat pump 4

Compressor A4Blocked
Cont. brine pump onNo
Compressor stop at brine°C-5
Brine pump on 10 daysOff


Heat pump 5

Compressor A5Blocked
Cont. brine pump onNo
Compressor stop at brine°C-5
Brine pump on 10 daysOff


Heat pump 6

Compressor A6Blocked
Cont. brine pump onNo
Compressor stop at brine°C-5
Brine pump on 10 daysOff


Heat pump 7

Compressor A7Blocked
Cont. brine pump onNo
Compressor stop at brine°C-5
Brine pump on 10 daysOff


Heat pump 8

Compressor A8Blocked
Cont. brine pump onNo
Compressor stop at brine°C-5
Brine pump on 10 daysOff


Heat pump 9

Compressor A9Blocked
Cont. brine pump onNo
Compressor stop at brine°C-5
Brine pump on 10 daysOff


Heat pump 10

Compressor A10Blocked
Cont. brine pump on")?>No
Compressor stop at brine°C-5
Brine pump on 10 daysOff


Heat pump 3

Compressor A3Blocked
Cont. brine pump onNo
Compressor stop at brine°C-5
Brine pump on 10 daysOff


Add heat

Start E1, degree minute-30
Diff E1, degree minute-100
Block add, outdoor°C5
Boiler, open mixing v.°C70
Boiler,max °C50
Tariff ELNo
Start at flue gas °C100


Solar panels

dT ma solar °C7
dT min solar °C3
Min speed pump %30
Ma boiler °C85
Ma DHW tank °C85
Ma buffer tank °C85
Max temp brine °C18
>>
<<
Time graph oper. min1
Flow l/mln6
Protection collector 


Pool

Pool temp °C22
Pool diff °C1.0
Pool priority °CLow


Frikyla

Cooling permit. from outdoorTOff
Primary flow temp at outdoor +2020
Primary flow temp at outdoor +4010
Min primary flow temperature18
Start coolig at overtemp1.0
Stop cooling at overtemp0.5


Skydd kollektor

Max Temp °C120
CoolingYes
RecoolingNo
Recooling to temp70
Anti-freeze")?>No
Anti-freeze °C-25


Heat pump

Compressor:Blocked
Brine pump on 10 days0
Tariff VPOn


Communication superior

MB address1
Baudrate9600
ParitetEven
Stop bit1


Inställningar

Save settings?

Settings

Load settings?

Inställningar

Hämta fabriksinställningar?

Define system

Def heating circuit 1

Heating circuit 1Yes
Room sensor 1 (B11)Yes
TypeWire


Def heating circuit 2

Radiator system 2 (Y2, G2)Yes
Room sensor 2 (B12)Yes
TypeWire


Def heating circuit 3

Radiator system 3 (Y3,G3)Yes
Room sensor 3 (B13)Yes
TypeWire


Def heating circuit 4

Radiator system 4 (Y4,G4)Yes
Room sensor 4 (B14)Yes
TypeWire


Def Heat pump

Heat pump 1On
Heat pump 2On
Heat pump 3On
Heat pump 4On
Heat pump 5On
Heat pump 6On
Heat pump 7On
>>


Def System type

Systeme type3
Def Add heat (E1)No
EcoMiniEl (E3)No
Additional heat 0-10V (E2)Yes
Heat pump for DHWA1
Heating flow during DHW (G1)No


Def DHW tank

DHW tank (B5)No
DHW circulation (G40)Yes
External buffer XYes


Def Solar panels

Solar panels (G30,B30, B31)No
Typeboiler
VaccumYes
Borehole recharge (Y31,G31)No


Def SMS

Activate GSM ?No


Service

Function test

Radiator system

Mixing valve1
Rad pump1Off
Mixing valve 2
Rad pump2Off
Mixing valve 3
Rad pump3Off
Mixing valve 4
>>


Heat pump to test

Heat pump to test1
Go to menu test


Test Heat pump 1

HP Compr.Off
HP Brine p.Off
HP Charge p.0


Test Valves

<
3-way valve (Y21)Ner
3-way valve (Y22)Ner


Test Additional Heat

Electric heater L1Off
0-10VOff
EcoMiniEl (E3)Off
Add heat DHW (E4)Off


Test DHW circ/ Solar/ Pool

DHW circulation pump (G40)Off
Solar panel pump (G30)57%
Solar heat exchanger pump (G32)57%
Solar 3-way valve (Y30)Heating
Solar charge borehole (Y31/G31)Off
Pool pumps and valve (G50/G51)Off


HEATPUMP

Select Id and OK to HP oper.Heat pump


Alarm log HP

Latest alarm:TimeHP(b)LP(b)SH(K)I(A)
 
Stored alarms:

Factory settings coded.

Settings coded compr.oper

Settings for heat pump idA1
Min brine in °C0.0
Max diff brine °C0.0
Max compr. temp °C120.0
Start delay10
Compressor type?
Diff HP in/out °C7.0
>>


HEATPUMP

Select Id and OK to HP oper.Heat pump


Log compressor stop

TypeAntal stoppSenaste
Stop, high compr temp0-
Stop, low evaporation0-
Stop, high evaporation0-
Stop, low suct gas exp.valve0-
Stop, low evapor exp.valve0-
Stop, high evapor exp.valve0-
Stop, low superheat exp.valve0-

Software update via USB

Insert USB and push OK.

Write log to USB

Write log to USBOff


Installation:

Primary flow °C (B1)0.0
Heating circuit 2 flow °C (B2)0.0
Room temp 1 °C (B11)0.0
Room temp 2 °C (B12)0.0
Outside Temp°C (B15)0.0
Solar Panel Outlet °C (B31)0.0
Solar Panel Inlet°C (B30)0.0